You don't have to return to the Workbench and do a project update in order for your changes to take affect. When you activate Dynamic Configuration, CIMPLICITY updates your project's configuration automatically. If a password is not required or if you enter the correct password, you will be able to dynamically configure the project. If a password is required a password dialog box will open when you use any of these methods. Click Tools>Dynamic on the Workbench menu bar.Click the Dynamic Configuration button on the Workbench toolbar.You cannot create or modify remote projects in Dynamic Update mode. You can also delete a class dynamically if there are no references to the class or there are no object instances of that class with composite references to the class. In Dynamic Update Mode you can modify all fields except Delay load.īeginning with CIMPLICITY v10.0, you can modify a class dynamically. In Dynamic Update Mode you can modify the following fields: Dynamic Configuration FunctionalityĬIMPLICITY supports the following dynamic changes: The Workbench provides you with the option to enable Dynamic configuration. right after the write request is sent out to the OPC. When configuration data is updated, the new entries are immediately available to other configuration functions, but they are not normally available to runtime functions. >Cimplicity OPC Server->Using the Cimplicity HMI OPC Server User. Note: When Dynamic mode is unavailable, or disabled, CIMPLICITY makes all configuration updates to files in the project's Master directory.